Voltage Drop Calculator

Estimate voltage drop for DC, single-phase AC or three-phase AC circuits. Use a conductor-size resistive model for planning, or enter resistance, reactance and power factor for a more detailed AC estimate.

V
A
ft
%
Ω/kft
Ω/kft

Voltage drop estimate

Load-end voltage0
Circuit resistance / effective impedance0
Voltage-drop percentage0
Voltage drop0

Planning estimate only. Voltage drop is not an ampacity, overcurrent-protection, conductor-sizing or code-compliance check. Electrical design and installation can be hazardous; verify the complete circuit with applicable rules, product data and a qualified professional.

Calculation breakdown

System0
One-way length0
Current0
Voltage0
Conductor / model0
Resistance component0
Reactance component0
Power factor0
Comparison limit0
Limit comparison0

Transparent formula

DC / 1φ resistive: Vdrop ≈ 2 × I × R × L

3φ resistive: Vdrop ≈ √3 × I × R × L

AC impedance: Vdrop ≈ factor × I × (R cosφ + X sinφ) × L

% drop = Vdrop ÷ source voltage × 100

0

What is voltage drop?

Voltage drop is the reduction in voltage between the source and the load as current flows through conductors and their electrical impedance. Longer runs, higher current and higher conductor resistance generally increase the drop. In AC systems, conductor reactance and load power factor can also matter.

A useful calculator should therefore do more than multiply distance by current. It should clearly define whether distance is one-way or round-trip, distinguish single-phase from three-phase circuits, expose the resistance assumptions and avoid confusing voltage-drop performance with conductor ampacity.

The basic DC voltage-drop formula

For a two-wire DC circuit with equal outgoing and return conductors:

Vdrop = 2 × I × R × L

Here, I is current, R is conductor resistance per unit length and L is the one-way circuit length. The factor 2 accounts for the outgoing and return path.

Single-phase AC voltage drop

For a simple resistive approximation, single-phase two-wire AC uses the same round-trip factor:

Vdrop ≈ 2 × I × R × L

For more detailed AC work, resistance alone may be insufficient. Southwire's cable guidance notes that AC voltage-drop calculations can require AC resistance, reactance and the load power factor.

Three-phase voltage drop

For a balanced three-phase system, the familiar line-to-line approximation uses √3 rather than the two-wire factor:

Vdrop ≈ √3 × I × (R cosφ + X sinφ) × L

When reactance is ignored and power factor is treated as unity, this reduces to:

Vdrop ≈ √3 × I × R × L

Why the calculator asks for one-way length

Many voltage-drop tools—including Cerrowire's—ask for the one-way circuit length. The formula itself then accounts for the return path in a two-wire circuit.

Common mistake: if you enter round-trip length into a formula that already multiplies one-way length by 2, the calculated drop is doubled.

Voltage-drop percentage

The absolute voltage drop is useful, but percentage makes circuits at different voltages easier to compare:

% voltage drop = voltage drop ÷ source voltage × 100

A 3 V drop on 120 V is 2.5%, while the same 3 V drop on 240 V is 1.25%.

Load-end voltage

The estimated voltage available at the load is:

Load-end voltage ≈ source voltage − voltage drop

This is a steady-state estimate. Starting currents, utility variation, transformer impedance, upstream feeder drop and changing loads can produce different measured values.

Conductor resistance and circular mil area

The conductor-size mode uses the familiar resistivity relationship:

R = K × L ÷ CM

K is a resistivity constant, L is conductor length and CM is conductor area in circular mils. Larger conductor area lowers resistance and therefore lowers voltage drop for the same current and distance.

The built-in model uses approximate copper and aluminum resistivity values at 20°C or 75°C for planning. It is not a substitute for the actual AC resistance data of a specific cable.

Why conductor temperature matters

Metal resistance rises with temperature. A conductor operating warm has greater resistance than the same conductor near room temperature, so a room-temperature voltage-drop calculation can be optimistic under load.

The simple mode lets you select an approximate temperature basis. For design work, use conductor data appropriate to the actual cable and operating conditions.

Copper versus aluminum

Copper and aluminum have different resistivities. For the same conductor area, aluminum generally has higher resistance, so equivalent voltage-drop performance often requires a larger aluminum conductor.

That does not mean this calculator should automatically choose a replacement size. Ampacity, termination ratings, connector compatibility and installation rules must also be checked independently.

AWG and kcmil

American Wire Gauge sizes become physically larger as the gauge number decreases. Beyond 4/0, large conductors are commonly expressed in kcmil. Cerrowire notes that kcmil and the older term MCM both refer to thousands of circular mils.

The conductor-size mode maps common AWG and kcmil sizes to circular-mil area solely for the resistive voltage-drop model.

Custom AC impedance mode

For AC circuits, the custom mode is the more transparent option when cable data is available. Enter AC resistance R, reactance X and load power factor.

Effective impedance term = R cosφ + X sinφ

where cosφ is the power factor and:

sinφ = √(1 − power factor²)

The calculator then applies the single-phase factor 2 or three-phase factor √3.

Why power factor changes AC voltage drop

With an inductive load, current is not perfectly in phase with voltage. The resistive and reactive parts of cable impedance therefore contribute differently to voltage drop.

Southwire's technical guidance specifically includes resistance, reactance and power factor in its AC approximation. This is why a calculator that assumes pure resistance for every AC circuit can hide an important assumption.

What resistance units should I enter?

In feet mode, custom resistance and reactance are entered in ohms per 1,000 ft. In metric mode they are entered in ohms per kilometre. The calculator converts the one-way circuit length to the matching basis before applying the formula.

Parallel conductors

When equal conductors are properly connected in parallel, the effective resistance and reactance of the parallel set decrease approximately in proportion to the number of identical parallel paths.

Reffective ≈ Rsingle ÷ number of parallel conductors

Parallel conductors are governed by installation and code requirements. The calculator only models their electrical effect after you provide the number of parallel paths.

Worked example: 120 V, 15 A, 100 ft

Suppose a two-wire circuit carries 15 A over a 100 ft one-way run. If the effective conductor resistance is 2 Ω per 1,000 ft, the round-trip resistance is:

2 × 2 Ω/kft × 0.1 kft = 0.4 Ω

The voltage drop is:

15 A × 0.4 Ω = 6 V

That equals 5% of 120 V, leaving an estimated 114 V at the load. This example illustrates the math only; it does not determine whether the conductor is acceptable for the circuit.

Worked three-phase example

For a 400 V balanced three-phase circuit, 30 A load, 50 m one-way length, 0.8 Ω/km resistance, 0.08 Ω/km reactance and 0.9 power factor:

sinφ = √(1 − 0.9²) ≈ 0.436 Zeffective = 0.8(0.9) + 0.08(0.436) ≈ 0.755 Ω/km Vdrop ≈ √3 × 30 × 0.755 × 0.05 ≈ 1.96 V

The percentage drop is about 0.49% of 400 V.

Voltage drop is not ampacity

This distinction is critical. Ampacity addresses how much current a conductor is permitted to carry under specified conditions. Voltage drop addresses circuit performance. A conductor can produce an attractive voltage-drop result and still be unsuitable because of ampacity, temperature, termination, protection or installation requirements.

Safety boundary: SonoCalculator intentionally does not label a wire size “safe,” “code compliant,” or “recommended” from voltage drop alone.

Why conductor sizing needs more checks

Real conductor selection can involve insulation rating, ambient temperature, number of current-carrying conductors, termination temperature limitations, overcurrent protection, continuous loads, motor requirements, short-circuit conditions, installation method and local rules.

Cerrowire's separate ampacity calculator illustrates how many parameters can be involved, and Southwire likewise warns that site-specific product approval remains with the responsible professional and authority having jurisdiction.

The 3% and 5% figures

In U.S. practice, 3% and 5% are commonly encountered voltage-drop design recommendations in NEC-related guidance: approximately 3% for a branch circuit and approximately 5% total for feeder plus branch circuit to the farthest outlet, depending on the applicable context.

These are not universal worldwide limits, and voltage-drop provisions can differ by circuit type and jurisdiction. The calculator therefore treats the percentage field as an optional comparison target that you control.

Why the comparison limit is user-controlled

A fixed green/red “pass” indicator can be misleading. A circuit may have a project specification tighter than 3%, or a different regulatory requirement may apply. Some sensitive equipment also needs tighter voltage performance.

Enter the target applicable to your project. The result merely reports whether the calculated percentage is above or at/below that number.

Motor circuits and starting current

Motors can draw substantially more current during starting than during normal operation. A steady-state current calculation may therefore understate the momentary voltage dip during startup.

Motor voltage-drop and starting-performance studies can require source impedance, motor characteristics and other system data. Do not treat a normal-running result as a motor-starting analysis.

LED lighting and sensitive electronics

Low-voltage lighting and electronics can be more sensitive to conductor drop because each lost volt represents a larger percentage of the source voltage. Driver behavior and allowable input range also matter.

Use the equipment manufacturer's voltage requirements rather than assuming a generic percentage is always acceptable.

Solar, battery and other DC systems

The two-wire resistive formula is useful for many simple DC runs. In low-voltage battery or solar circuits, even a small absolute drop can represent a significant percentage and waste power as heat.

But conductor ampacity, protective devices, polarity, fault current and equipment-specific rules still require separate checks.

Power loss in conductors

For a resistive path, conductor loss is related to current squared:

Ploss = I² × Rpath

This explains why higher current can sharply increase losses. However, the calculator's primary purpose is voltage drop, not thermal conductor design.

Long runs

Cerrowire notes that voltage drop becomes increasingly important on long runs such as circuits to outbuildings or pumps. Longer length increases total conductor resistance directly.

For very long or complex AC circuits, distributed cable effects and system modeling may justify more advanced engineering methods than the simplified equations here.

Multiple loads along one circuit

A circuit with loads tapped at different points does not carry the same current along its entire length. A single “total current × total length” calculation can therefore overstate or misrepresent individual segment drops.

Calculate each segment with the current actually flowing through that segment, then sum the voltage drops along the path to the load being evaluated.

Unbalanced three-phase systems

The standard √3 formula assumes a reasonably balanced three-phase system. Significant phase imbalance, neutral current, harmonics or nonlinear loads may require phase-by-phase analysis.

The calculator does not model those advanced conditions.

Why measured voltage can differ

Actual load voltage can differ from the calculation because source voltage changes, conductor temperature changes, connections add resistance, loads vary and upstream feeders or transformers also have impedance.

A calculation is a design estimate; field measurement under appropriate safe procedures is a different form of verification.

Common voltage-drop mistakes

How to verify a voltage-drop calculation

First confirm the circuit topology: DC two-wire, single-phase or balanced three-phase. Confirm that the entered distance is one-way. Verify current and nominal voltage.

Then verify conductor data. For a basic estimate, check conductor material and area. For AC work, use cable-manufacturer resistance and reactance data when available. Finally, compare the result with the performance target and separately perform every required ampacity, protection, termination and installation check.

Frequently asked questions

What is the formula for voltage drop?

For a simple two-wire resistive circuit, Vdrop ≈ 2IRL. For balanced three-phase, Vdrop ≈ √3IRL. AC impedance calculations can add resistance, reactance and power factor.

Do I enter one-way or total wire length?

Enter one-way circuit length. The two-wire formula accounts for the return path with its factor of 2.

What is a good voltage-drop percentage?

It depends on the applicable standard, project and equipment. U.S. NEC-related design guidance commonly references 3% branch-circuit and 5% feeder-plus-branch recommendations, but those figures are not universal.

Can this calculator choose my wire size?

No. It calculates voltage-drop performance for a size you enter. Safe conductor selection also requires ampacity and other electrical-design checks.

Does it support aluminum wire?

Yes, in the simplified resistive model. Actual cable data should be used when greater precision is required.

Does it support three-phase?

Yes, for balanced three-phase voltage-drop estimates using the √3 relationship.

Why is there a power-factor input?

In AC circuits, resistance and reactance contribute according to the phase relationship between current and voltage. Power factor provides cosφ for the approximation.

Is voltage drop the same as power loss?

No. They are related but different. Resistive power loss follows I²R, while voltage drop is the reduction in voltage along the circuit.

Can I use this for motor starting?

Not as a complete motor-starting study. Starting current and source/system impedance can require more detailed analysis.

Is the result code compliant?

The calculator does not make that claim. Electrical requirements vary by jurisdiction and application, and voltage drop is only one part of circuit design.

Final note: use this calculator to make voltage-drop assumptions visible—not to replace electrical design. Confirm one-way length, load current, system type and conductor impedance, then separately verify ampacity, overcurrent protection, terminations, installation method, equipment requirements and the rules that apply to the project.